136 ACS550-01/U1 User’s Manual
Parameters
2208 EMERG DEC TIME
Sets the deceleration time for maximum frequency to zero for an emergency.
See parameter 2109 EMERG STOP SEL.
Ramp is linear.
2209 RAMP INPUT 0
Defines control for forcing the speed to 0 with the currently used deceleration ramp (see parameters 2203
DECELER
TIME 1 and 2206 DECELER TIME 2).
0 =
NOT SEL – Not selected.
1 =
DI1 – Defines digital input DI1 as the control for forcing the speed to 0.
• Activating the digital input forces the speed to zero, after which the speed will stay at 0.
• De-activating the digital input: speed control resumes normal operation.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for forcing the speed to 0.
•See
DI1 above.
7 =
COMM – Defines bit 13 of the Command Word 1 as the control for forcing the speed to 0.
• The Command Word is supplied through fieldbus communication.
• The Command Word is parameter 0301.
-1 =
DI1(INV) – Defines inverted digital input DI1 as the control for forcing the speed to 0.
• De-activating the digital input forces the speed to 0.
• Activating the digital input: speed control resumes normal operation.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for forcing the speed to 0.
•See
DI1(INV) above.