1SCR
2AI1
3AGND
4 10V
5AI2
6AGND
7AO1
8AO2
9AGND
10 24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
External speed reference 1: 0…10 V
Reference voltage 10 V DC
Motor output speed: 0
…20 mA
Speed/torque control: Activation selects torque control
Constant speed 1: 1202
Relay output 1, programmable
Default operation:
Relay output 2, programmable
Default operation:
Relay output 3, programmable
Default operation:
Output current: 0
…20 mA
Ready =>19 connected to 21
Running =>22 connected to 24
Fault (-1) =>25 connected to 27
Analog input circuit common
External torque reference: 4…20 mA
Analog output circuit common
Auxiliary voltage output +24 V DC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
Note 1.
• Reverses rotation direction in
speed control.
• Reverses torque direction in
torque control.
Start/stop: Activation starts the drive.
Forward/reverse: Activation reverses direction
1
Ramp pair selection: Activate to select 2nd acc/dec ramp pair
Run enable: Deactivation always stops the drive
(Fault => 25 connected to 26)
Note 2.
The sensor for AI2 is powered
externally. See the manufacturer’s
instructions. To use sensors supplied
by the drive aux. voltage output, see
page 82.
2
X1
1…10 kohm
Comentários a estes Manuais