Start-up and control panel 71
ACH550-01 User's Manual
For detailed hardware description, see chapter Technical data.
Note: The current parameter value appears below the
highlighted parameter.
Note: To replace the displayed value of a parameter with the
default value, press the UP/DOWN keys simultaneously.
Note: The most typical and necessary parameters to change are
the following parameter groups: Group 99: START-UP DATA,
Group 10: START/STOP/DIR, Group 11: REFERENCE
SELECT, Group 13: ANALOGUE INPUTS, Group 16: SYSTEM
CONTROLS, Group 20: LIMITS, Group 22: ACCEL/DECEL,
Group 40: PROCESS PID SET 1, Group 41: PROCESS PID
SET 2 and Group 42: EXT / TRIM PID.
Note: To restore the default factory settings, select the HVAC
default application macro.