ABB RCNA-01 Manual do Utilizador Página 176

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 474
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 175
172 Parameter listing and descriptions
ACH550-01 User's Manual
Group 03: FB ACTUAL SIGNALS
This group monitors fieldbus communications. See also chapter
Serial communications.
Code Description Range
0301 FB CMD WORD 1 -
Read-only copy of the Fieldbus Command Word 1
The fieldbus command is the principal means for controlling the drive
from a fieldbus controller. The command consists of two Command
Words. Bit-coded instructions in the Command Words switch the
drive between states.
To control the drive using the Command Words, an external location
(
EXT1 or EXT2) must be active and set to COMM. (See parameters
1001 and 1002.)
The control panel displays the word in hex. For example, all zeros
and a 1 in Bit 0 display 0001. All zeros and a 1 in Bit 15 display 8000.
0302 FB CMD WORD 2 -
Read-only copy of the Fieldbus Command Word 2
See parameter 0301.
Bit # 0301, FB CMD WORD 1 0302, FB CMD WORD 2
0STOP FBLOCAL_CTL
1START FBLOCAL_REF
2 REVERSE START_DISABLE1
3 LOCAL START_DISABLE2
4 RESET Reserved
5 EXT2 Reserved
6 RUN_DISABLE Reserved
7 STPMODE_R Reserved
8 STPMODE_EM Reserved
9 STPMODE_C Reserved
10 RAMP_2 Reserved
11 RAMP_OUT_0 REF_CONST
12 RAMP_HOLD REF_AVE
13 RAMP_IN_0 LINK_ON
14 RREQ_LOCALLOC REQ_STARTINH
15 TORQLIM2 OFF_INTERLOCK
Vista de página 175
1 2 ... 171 172 173 174 175 176 177 178 179 180 181 ... 473 474

Comentários a estes Manuais

Sem comentários