Serial communications 155
ACH550-01 User's Manual
4016 ACT1 INPUT 1…7
Defines the source for actual value 1 (
ACT1).
6=
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT1.
Value is not scaled.
7=
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT1.
Value is not scaled.
4017 ACT2 INPUT 1…7
Defines the source for actual value 2 (
ACT2).
6=
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT2.
Value is not scaled.
7=
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT2.
Value is not scaled.
Code Description Range
4110,
4114,
4116,
4117
These parameters belong to PID parameter set 2. The operation is
analogous with set 1 parameters 4010, 4014, 4016 and 4017.