276 Parameter listing and descriptions
ACH550-01 User's Manual
Analogue input reference correction
Parameter values 9, 10, and 14…17 use the formula in the following
table.
Where:
• C = Main reference value
(=
COMM for values 9, 10 and = AI1 for values 14…17)
• B = Correcting reference
(=
AI1 for values 9, 10 and = AI2 for values 14…17).
Example: The figure
shows the reference
source curves for
value settings 9, 10,
and 14…17, where:
•C = 25%.
• P 4012
SETPOINT
MIN = 0.
• P 4013
SETPOINT
MAX = 0.
• B varies along the
horizontal axis.
4011 INTERNAL SETPNT unit and scale defined
by par 4006 and 4007
Sets a constant value used for the process reference.
• Units and scale are defined by parameters 4006 and 4007.
4012 SETPOINT MIN -500.0…500.0%
Sets the minimum value for the reference signal source. See parameter
4010.
4013 SETPOINT MAX -500.0…500.0%
Sets the maximum value for the reference signal source. See
parameter 4010.
Code Description Range
Value setting Calculation of the AI reference
C + B C value + (B value - 50% of reference value)
C
*
B C value · (B value / 50% of reference value)
C - B (C value + 50% of reference value) - B value
C / B (C value · 50% of reference value) / B value
120
100
80
60
40
20
0
0
100%
9, 14 (+)
16 (-)
10, 15 (
*
)
17 (/)
B