Starting up the FPBA-01 adapter for different communication profiles
21
Starting up the FPBA-01 adapter for different
communication profiles
Overview
This chapter presents the steps to take during the start-up of the FPBA-01
PROFIBUS DP Adapter Module with the drive. For more detailed information, see
PROFIBUS DP Adapter Module FPBA-01 User’s Manual (3AFE68573271
[English]).
WARNING! Follow the safety instructions given in this manual and in the hardware
manual of the drive.
Mechanical and electrical installation
• Insert the FPBA-01 into its specified slot in the drive.
• Fasten the screw.
• Plug the fieldbus connector to the module.
Drive configuration
• Power up the drive.
• A parameter must be adjusted to activate the communication: set parameter
50.01 FBA ENABLE to ENABLE.
• Parameter group 51 shows the status of the FPBA configuration parameters.
• At minimum, set the required node address at parameter 50.02 NODE ADDRESS
and the communication profile at 5105 PROFILE. Finally, validate the settings
with 51.27 FBA PAR REFRESH.
Cyclic data handling
With the FPBA-01, both data-consistent and non-consistent communication can be
used, data-consistent meaning that the whole cyclic data frame is transmitted during
a single program cycle. Some PLCs handle this internally, but others must be
programmed to transmit data-consistent telegrams (for more information, see
PROFIBUS DP Adapter Module FPBA-01 User’s Manual (3AFE68573271 [English])
chapter Commmunication).