ABB FPBA-01 Manual do Utilizador Página 32

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 126
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 31
Electrical installation
32
Bus termination
Bus termination is required to prevent signal reflections from the
bus cable ends. The FPBA-01 module is not equipped with
internal bus termination. Therefore, the D-SUB connectors at the
first and last modules of the bus must have built-on termination
switched on. See the diagram below.
The FPBA-01 module is able to supply power for an active-type
termination circuitry (30 mA max.).
Figure 3. PROFIBUS cable termination
Note: Further information on PROFIBUS wiring is available from
the publication “PROFIBUS RS 485-IS User and Installation
Guideline” (www.profibus.com, order no. 2.262).
PROFIBUS
device
ON
PROFIBUS
device
OFF
PROFIBUS
device
ON
PROFIBUS
device
OFF
Ter m . Ter m. Ter m . Ter m .
Vista de página 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 125 126

Comentários a estes Manuais

Sem comentários