©ABB Ltd -27
E-Clipse Bypass – Communications Set-up
Set-up Drive external communications (through bypass)
Bypass parameter 5302
Set desired drive unique network ID (must be different than bypass
node number) Default = 1 for most protocols
For BACnet only, you must set additional parameters
Set desired Baud Rate 5303 = 9.6; 19.2; 38.4; or 76.8 kB
On ModBus systems, you may also need to set baud rate
BACnet Drive Device Object Instance ID – Bypass parameter
5311 / 5317
Set desired drive Device Object Instance ID
Cycle power if no communications is required to bypass
objects (points)